2GSB010160A0022 - Tụ Bù ABB CMLD63 440 70

Tình trạng: Còn hàng

Sku: 3008

Danh mục: CLMD -Tụ Bù Hạ Thế - RVC Bộ điều khiển tụ bù

Giá: Liên hệ

Mô tả chi tiết

2GSB010160A0022 - Tụ Bù ABB CMLD63 440 70

Tụ bù ABB CLMD63 440 70
- Mã sản phẩm: 2GSB010160A0022
- Thương hiệu: ABB
- Xuất xứ: Thái Lan
- Điện áp định mức: 440V 50Hz 3p
- Công suất bù: 70kVAr
- Cấp bảo vệ IP42
- Chịu đươc quá áp 1.1 Un và quá dòng 1.3In
- Đáp ứng tiêu chuẩn IEC 831-1, IEC 831-2
- Bảo hành: 12 tháng

Technical specifications
Voltage rangeFrom 220 to 1000 V
Frequency50 and 60 Hz
ConnectionThree-phase as standard construction (single-phase on request)
Discharge resistorsPermanently connected built-in discharge resistors are sized to ensure safe discharge of the capacitor to less than
50V in 1 minute after a switch off
Minimum time between disconnection and re-energization: 40 seconds
TerminalsCLMD13: three M6 terminals
CLMD33S: three cable outputs (6, 10, 16 mm²), 50 cm long
CLMD43-53-63-83: with threaded rods M6, 8, 10 or 12 according to the power of the capacitor
EarthCLMD13-33S: earth connection on the enclosure fxation
CLMD43-53-63-83: a M8 terminal is included under the cover
Cable inputBy a knock out:
CLMD13: 22.5 mm
CLMD33S: 500 mm
CLMD43-53: 37 mm
CLMD63-83: 47 mm
Case materialZinc electroplated mild steel
ColorBeige RAL 7032
FixingCLMD13: with two slots, diameter 6.5 mm (suitable fxing for assembly in module)
CLMD33S: with eight fxation holes, diameter 5.4 mm
CLMD43-53-63-83: with two slots 26 X 12 mm
ExecutionIndoor (outdoor on request)
ProtectionCLMD13-43-53-63-83: IP 42 (IP 54 on request)
CLMD33S: IP40
Maximum ambient temperatureClass „D“ (+55°C) according to IEC 60831
Minimum ambient temperatureIndoor type: -25°C
Outdoor type: -40°C
Minimum distance between unitsCLMD13-33S: 20 mm (25 mm for units > 30 kvar)
CLMD43-53-63-83: 50 mm
Minimum distance between units
and wall
CLMD13-33 : 20 mm (25 mm for units > 30 kvar)
CLMD43-53-63-83: 50 mm
Losses (discharge resistors included)< 0.5 Watt/kvar for 380 V rated voltage and above
Tolerance on capacitance0 % + 10 %
Voltage testBetween terminals: 2.15 Un for 10 seconds.
Between terminals and earth: 3 kV for 10 seconds for UN < 500 V and 4 kV for 10 seconds for UN > 500 V
Lightning impulse voltage testCLMD13-43-53-63-83: 15kV
CLMD33S: 8kV
The acceptable overloads are those
specified in IEC 831-1&2
Overvoltage tolerance: 10% max. at intervals
Overcurrent tolerance: 30% permanently
Maximum overload: stable operation at 135% of the nominal rating (generated by overvoltages and harmonics)